Skip to main content
Home
Our Divisions
State Fire Marshal
Fire Code
Fire Code Information By Topic
Carbon monoxide detection in child care occupancies

Fire code

Carbon monoxide detection in child care occupancies

This flow chart is designed to aid code officials, architects, design professionals and others in navigating the Minnesota State Fire Code (MSFC).

  • This flow chart applies to new Group E and I-4 child daycare and K-12 classrooms.
  • Carbon monoxide alarm: A single- or multiple-station alarm intended to detect carbon monoxide gas and alert occupants by a distinct audible signal. It incorporates a single unit's sensor, control components, and an alarm notification appliance.
  • Carbon monoxide detector: A device with an integral sensor to detect carbon monoxide gas and transmit an alarm signal to a connected alarm control unit.

CO detection system requirements 

  • CO detectors shall be installed in Group E and I-4 occupancies except as allowed per Fire Marshal Code Advisory Panel (FMCAP) 20-008-I, which is found at the end of this flow chart.  It is important to note that single- or multiple-station CO alarms are prohibited in any other instance within these occupancies.
  • Standard: NFPA 720, CO detectors listed to UL 2075.
  • Locations: As specified in MSFC Section 915.2.
  • Combination detectors: Listed to UL 268 and UL 2075.
  • Notification appliances shall be installed in the area(s) where the detection devices are installed.
  • The system shall annunciate to a constantly attended location or supervising station.

General CO detection location requirements

  • Detectors within each classroom and automatically transmitted to an on-site staffed location.
    • Exception: Not required to be transmitted when total occupant load is 30 or less.

When required, there are alternate CO detection location requirements for Group E and I-4 child daycare and K-12 school classrooms. More than one of the conditions below may apply.

  • When a forced air fuel-burning appliance serves such buildings.
    • Alternate: Single point detection approved in first room or area served by the main supply duct from the furnace.
  • When such buildings contain a fuel-burning appliance.
    • Exception 1: CO detection is not required when there are no communicating openings between the fuel-burning appliance(s) and the rest of the building.
    • Alternate 1: Detector in approved location between the fuel-burning appliance(s) and classrooms.
    • Alternate 2: Detector located on the ceiling of rooms containing the fuel-burning appliance(s).
  • When such buildings have an attached garage.
    • Exception 1: CO detection is not required when there are no communication openings between the garage and classrooms.
    • Exception 2: CO detection is not required when classrooms are more than 1-story above or below the garage.
    • Exception 3: CO detection is not required when the garage is attached to classrooms by an open-ended corridor (breezeway).
    • Alternate: Detector in approved location between garage and classrooms.
    • Exempt garages: Open parking garages or enclosed garages complying with Minnesota Building Code Section 406.4.

Maintenance

  • Enclosed garage detection: Maintained in accordance with Minnesota Mechanical Code Section 404.1, manufacturer instructions and listing.
  • End-of-life: Devices that become inoperable or sound end-of-life signals shall be replaced. 

Group E occupancies

  • Where such conditions require the installation of CO detection in Group E occupancies and:
    • The Group E occupancy is required or provides an NFPA 72 fire alarm system, CO detectors shall be provided in accordance with the requirements of MSFC Section 915 or
    • Group E occupancy is not required and doesn’t provide an NFPA 72 fire alarm system. CO alarms shall be permitted when
      • CO alarms complying with the requirements of MSFC 915.4.1 and 915.4.2 are installed in every room or area providing care or instruction
      • The required fire safety plan includes manufacturer information regarding the testing, inspection, and maintenance of such CO alarms
      • The fire inspection report issued by the Authority Having Jurisdiction shall detail such requirements per MSFC 104.8.

Questions?

You can email us with your Minnesota State Fire Code questions. Code staff monitor this email address ​regularly and will respond to your question. During busier times, it may take up to a week before we are able to respond. If you don't hear back from us after one week, please let us know. Thanks for your patience.